Product FAQ
You are here : Home > Product FAQ > Can the radar be used directly after installation?

Can the radar be used directly after installation?

Time:2026-08-07  Browse: 178

Answer: Additional configuration is required: set the installation height; calibrate current for 4‑20 mA output models.

Installation height: Vertical distance from the water bottom to the radar hemisphere. After inputting this value, the system automatically calculates water depth via the current empty distance:

Water Depth = Installation Height – Empty Distance

Water depth: Vertical distance from the water bottom to the water surface. After inputting this value, the system automatically calculates installation height via the current empty distance:

Installation Height = Water Depth + Empty Distance

Only one of the two parameters above needs to be configured.

Precautions:

The set installation height cannot exceed the radar’s full measuring range.

Internal resistance varies between third-party display meters; perform an on-site current calibration matching the actual meter.

Configuration menus:

Installation height: Upper Computer – Installation Height / Bluetooth – Water Level Configuration – Installation Height

4‑20 mA current calibration: Bluetooth – 4‑20 mA Output Calibration – Current Calibration

Related reading

At a glance: a radar cannot be used directly after installation — you must set the installation height and, for 4–20 mA models, calibrate the current endpoints. Without these, the reading or output is wrong.

Step-by-step diagnosis

  1. Record the vertical distance from the water/tank bottom to the radar hemisphere (installation height).
  2. For 4–20 mA models, note the empty and full levels.
  3. Enter the installation height in the configuration.
  4. Calibrate the 4 mA / 20 mA endpoints against empty and full.

How to fix it

Set the installation height

This tells the transmitter where zero level is, so the displayed distance is correct.

Calibrate 4–20 mA endpoints

Map the level reading to 4 mA (empty) and 20 mA (full) so the output is linear.

Verify against a known level

After setup, check the reading at a known fill point before commissioning.