Answer: Possible causes:
Obstacles between the sensor and the target weaken reflected echo energy.
The sensor is not parallel to the target surface, leading to weak reflected echoes.
The measured target is not a flat solid surface or liquid surface.
The water level rises too high and submerges the probe.
Solutions:
Verify vertical/horizontal installation of the device; ensure no obvious obstructions on the radar probe.
Weak echoes in open environments may stem from antenna echo interference; increase RF transmit power.

At a glance: the “Insufficient Echo Energy” alarm means the radar received a reflected signal too weak to compute a reliable distance. It is almost always an installation or tank-condition issue — not a hardware fault.
Keep the beam path clear. For unavoidable internal structures, enable spurious echo learning so the transmitter ignores the fixed reflection and locks onto the moving surface echo.
Re-mount the sensor vertical to the surface. In narrow wells or stilling tubes, centre it so the beam does not clip the wall.
In open environments — rivers, open water tanks — weak echoes often come from antenna echo interference. Raising the RF transmit power recovers the true target echo. Leave it at the factory default otherwise.
Set the installation height so the maximum level never reaches the antenna. For tanks that fill to the top, use a longer stilling tube or a side-mounted sensor.
For persistent weak echoes — foam, low-dielectric liquids, or long measuring ranges — an 80 GHz FMCW unit with higher effective radiated power is the practical choice. Review the Jiajia Eye 80 GHz radar level transmitter range, or contact our application engineers with your tank drawing for a free selection check.