Time:2026-08-07 Browse: 215
Answer: Our 80G radar operates at 76‑81 GHz and outputs valid data 1 second after power-on. Amplitude limiting filtering is enabled by factory default to smooth readings. Disable filtering for faster response — measurement accuracy remains unchanged, though transient interference echoes may be captured.
Factory filtering purpose: Water levels rise/fall gradually; filtering smooths sudden data jumps.
Limiting filter: Eliminates short-term abnormal data spikes.
Sliding-window averaging filter: Further smooths data changes on top of amplitude limiting filtering.
To disable filtering:
Upper computer: Set Variation Range and Duration to 0, save all settings; send AT command AT+SLIDWINFILTERNUM=0.
Bluetooth app: Set Amplitude Limit Filter Threshold (CM), Amplitude Limit Filter Count, Sliding Average Filter Window all to 0, then save.
At a glance: an 80 GHz radar outputs valid data about 1 second after power-on; if it feels slow, the amplitude-limiting filter (on by default) is smoothing the reading. Disabling it speeds response at the cost of some noise.
Default smoothing removes jitter in normal operation.
If you need quicker reaction, turn off amplitude limiting and accept more noise.
A ~1 s startup is by design, not a fault.
For persistent issues on this topic, review the Jiajia Eye 80 GHz radar level transmitter range, or send our application engineers your tank drawing and process data for a free configuration check.