Level Jumps 50 cm Beside an Agitator: A Real Echo Under the Threshold

You are here : Home > Radar & Ultrasonic Level Meter FAQ Hub > Radar Level Sensor Field Cases: Real Sites, Real Fixes > Level Jumps 50 cm Beside an Agitator: A Real Echo Under the Threshold
Application: liquid level in a tank with a vertical agitator
Device: JJY-YLD128D-1.5 radar level transmitter
Mounting height: 0.72 m
Symptom: empty distance reads −1, level jumps more than 50 cm
Recorded: 4 November 2026

The problem

Site & symptom

Mounting height 0.72 m, real empty distance 0.23 m with the liquid flowing and the agitator stopped. The transmitter frequently reported an empty distance of −1, and when it did produce a number the level jumped by more than 50 cm from one reading to the next.

A tank 0.72 m deep cannot change level by 50 cm while the liquid is flowing quietly. The jumps were not the process – they were the unit losing and re-finding a target.

Root cause

The Bluetooth diagnostic page reported insufficient echo energy: the real return was weak, not absent.

The antenna threshold on the unit was 200. A weak return close to that threshold is intermittently accepted and intermittently rejected – which is exactly the pattern seen here: one sweep returns a value, the next returns nothing and the output falls to −1.

Installation and geometry were checked and were as specified: conventional mounting, blind zone at its minimum of 0.05 m. So the problem was not the setup, it was the strength of the return from a surface close to the antenna inside a tank fitted with an agitator.

The installation

Tank with a vertical agitator, the radar sensor circled in red at the top
Field case – still from the site video, sensor circled. The vertical agitator fills the centre of the tank, and its shaft and blades sit directly in the beam path.

How we fixed it

Solution

Two steps, in this order: cleared the false echoes recorded in the unit, then selected the real target so the unit tracks the liquid surface and nothing else.

The mounting advice that went back to site: keep the antenna clear of the agitator and a little away from the tank wall. A weak return in a small tank is usually a geometry problem before it is a device problem – the beam is spending part of its energy on the shaft, the wall or the fittings instead of the surface.

Result

The unit held the real target and the level stopped jumping. On the after-capture the real echo is the one the unit is tracking, with the false returns cleared out of the record.

Echo spectrum: before and after

FFT spectrum before clearing false echoes, real return close to the threshold
Before – the red trace is the live return and the real echo is weak against competing returns.
FFT spectrum after selecting the real target
After clearing the false echoes and selecting the real target – the tracked echo is separated from the rest.

What this case teaches

  • −1 is not a measurement. When the empty distance output goes negative, the unit is telling you it has no valid target – do not read it as a level below the antenna.
  • A real echo can be too weak to trust. “Insufficient echo energy” means the return exists but sits near the antenna threshold; the reading will flicker in and out rather than fail cleanly.
  • Being inside the blind zone spec is not the same as being reliably measured. A 0.23 m empty distance against a 0.05 m blind zone is geometrically valid, and still marginal if the return is weak.
  • In an agitated tank, aim first. The shaft and blades take energy out of the beam. Moving the antenna clear of them often does more than any parameter change.

Level that flickers between a value and −1, or jumps tens of centimetres in a small tank? Send us the mounting height, the agitator position and a spectrum capture – we will tell you whether the return or the setup needs work.