A solar-powered radar flow meter on a river channel reported an empty distance of 4.5 m. Measured on site the empty distance was 3 m, with 2 m of water in the channel.
The customer’s complaint was about the level, but the level was not what was wrong. Two separate setup errors were sitting behind it.
First error – the mounting height was set to 3 m. That is the empty distance, not the mounting height. With 2 m of water in the channel the sensor stands roughly 5 m above the channel bed, so a 3 m mounting height cannot describe this installation. Every figure the unit derives from that number inherits the error.
Confusing the two is common because both are a distance from the sensor downwards: empty distance is sensor to water surface, mounting height is sensor to the bottom of the channel. The gap between them is the water depth – and it changes all day.
Second error – the flow plate was installed backwards. The velocity plate has to face into the flow. Fitted the other way round it reads the wrong direction of travel, and the flow figure is wrong even when the level is right.


First we checked the signal, because a bad reading is usually a bad echo: the spectrum was clean, one well-formed peak. That ruled out the water surface as the problem and pointed at configuration.
Then, in order: explained the difference between empty distance and mounting height so the site could fill in the right figure, had them re-measure the installation, and had them turn the flow plate round to face upstream.
The mounting advice that went with it: keep the beam square to the water surface, keep it clear of banks, vegetation and structures that return an echo of their own, and fit the velocity plate against the flow.
Correct level readings after the setting was corrected, and correct flow direction after the plate was reversed. Nothing was replaced – both faults were installation and configuration.