Indoor Water Level Jumps to Zero: A 14 m Echo Inside an Oversized Span

You are here : Home > Radar & Ultrasonic Level Meter FAQ Hub > Radar Level Sensor Field Cases: Real Sites, Real Fixes > Indoor Water Level Jumps to Zero: A 14 m Echo Inside an Oversized Span
Industry: industrial water level
Application: indoor water tank
Device: JJY-YLD128HS-1.5 radar level sensor, firmware 20250616
Symptom: reading intermittently drops to zero
Recorded: 3 November 2026

The problem

Site & symptom

Indoor water level measurement, mounting height 9.8 m. The unit occasionally jumped to zero – not drifting and not noisy, just a 0 with no level behind it. The rest of the time it read normally, which is what made it hard to catch.

Root cause

The echo spectrum showed a fixed echo around 14 m. The unit had been configured with a 30 m span, so the sampling window reached well past 14 m and picked that echo up on every sweep.

That echo sits farther away than the 9.8 m mounting height. Once the unit locked onto it, the derived empty distance could come out larger than the actual mounting height – a value the installation cannot physically have, and the output fell to 0.

The firmware build had an echo-learning function intended to filter fixed false echoes. On this build it did not remove this one, so the false echo stayed in the picture sweep after sweep.

The installation

Radar level sensor mounted on the structure above an indoor water tank, photographed through a safety net
Field case – the sensor on the structure above the water surface, seen through the safety net. Indoors there is no open sky to reflect from, but a fixed structure at 14 m does the same job.

How we fixed it

Solution

Changed the span from 30 m to 12 m.

That is the whole fix. With a 12 m span the sampling window stops short of the 14 m echo, so the false echo is never sampled. The real target – the water surface, always inside the 9.8 m mounting height – stays well within range.

No gain change and no re-learning. The echo was never the problem; the window that included it was.

Result

The reading stopped dropping to zero, and the spectrum settled to a single dominant peak.

Echo spectrum: before and after

Phone screenshot of the FFT spectrum before the fix, showing two strong peaks
Before – two peaks in the window. The extra one is the fixed echo that the 30 m span was still reaching.
Phone screenshot of the FFT spectrum after the fix, showing one dominant peak
After the span change – one dominant peak, and the false echo is outside the window.

What this case teaches

  • A long span is not free. Every extra metre of span is another metre in which a fixed echo can be sampled and mistaken for the product surface.
  • Match the span to the installation height, not to what the site might need one day. This unit needed 9.8 m and was configured for 30 m – 20 m of empty window for something to go wrong in.
  • A reading that drops to zero is often not a communication fault. Check whether the reported empty distance is larger than the mounting height – if it is, the unit is describing a target that cannot exist.
  • Echo learning cannot rescue a span that is too long. If the echo is inside the window, the unit still sees it. Shorten the window.

Seeing an occasional zero, a value that exceeds the tank height, or a fixed echo that will not learn out? Send us the mounting height, the configured span and a spectrum capture – we will tell you which one to change first.

Talk to an application engineer