Answer: Additional configuration is required: set the installation height; calibrate current for 4‑20 mA output models.
Installation height: Vertical distance from the water bottom to the radar hemisphere. After inputting this value, the system automatically calculates water depth via the current empty distance:
Water Depth = Installation Height – Empty Distance
Water depth: Vertical distance from the water bottom to the water surface. After inputting this value, the system automatically calculates installation height via the current empty distance:
Installation Height = Water Depth + Empty Distance
Only one of the two parameters above needs to be configured.
Precautions:
The set installation height cannot exceed the radar’s full measuring range.
Internal resistance varies between third-party display meters; perform an on-site current calibration matching the actual meter.
Configuration menus:
Installation height: Upper Computer – Installation Height / Bluetooth – Water Level Configuration – Installation Height
4‑20 mA current calibration: Bluetooth – 4‑20 mA Output Calibration – Current Calibration